Sales/Inquiries: (281) 332-0999
   
 
SLC II Load Center Datasheet
 
SLC II Main Breaker Load Centers with Lighting Control are UL Listed and conform to all applicable NEMA specifications. Specifically designed to provide convenient multi-circuit breaker protection and photocell operated lighting control in one unit.

Enclosure Features

  • NEMA 12 enclosure fabricated from 14 ga. galvanized steel or 14 ga. T-304 stainless includes integral drip shield for protection against rain and snow.
  • Continuous hinge design provides easy access to breakers and selector switch.
  • Hasp and staple are provided for padlocking
  • Standard Size is 36"H x 14-1/2"W x 7-3/8"D (914mm x 368mm x 187mm) to provide ample space for wiring requirements.
  • Mounting tabs on top and bottom of enclosure.
  • Accepts incoming power from 120/240 VAC single phase source.

Load Center Features

  • Factory installed 2-pole main breaker with 70 Amp or 100 Amp continuous rating. Factory installed branch breaker for lighting control circuitry with 20 Amp continuous rating.
  • Ample space for adding plug-in breakers. Available space for installing up to 13 single pole breakers or 6 double pole breakers.
  • Branch breakers available in single or double pole up to 70 Amps.
  • Rated for 120/240 Volts AC, single phase, 3-wire with neutral and grounding provisions.
  • Incoming power is fed through main breaker via mechanical solderless type lugs approved for Cu or Al conductors. Lugs accept incoming wire sizes from #4 through #2/0.
  • "Dead-Front" trim for personnel protection.
  • One piece plated copper bus.
  • 22,000 RMS sym. Amperes short circuit current rating.
  • Accepts Square D "QO&" series plug-in branch circuit breakers.
  • NEMA 1 Enclosed Lightning Arrestor pre-wired ahead of Load Center  

Lighting Control

  • Photocell with twist-lock mounting base
  • 20 Amp, 2-pole breaker for circuit protection
  • 30 Amp NEMA Rated Lighting Contactor w/ 120 VAC Coil (20 Amp Tungsten Lighting Rating)
  • Separate Dead Front for Lighting Control Section
  • H-O-A Selector Switch for Lighting Control Operation
  • Separate 10 Amp Breaker for Control Circuitry
  • Plexiglass photocell viewing ports on both sides of enclosure
  • Termination points for up to 10 pairs of #12 awg lighting control wires.

Applicable Standards

All SLC II Main Breaker Load Centers with Lighting Control meet or exceed the following standards:

  • NEC
  • Federal Specifications WP-115c, Type 1, Class 2
  • UL 508 and UL Service Entrance Equipment