| SLC II Main Breaker Load Centers with Lighting Control are UL Listed and conform to all applicable NEMA specifications. Specifically designed to provide convenient multi-circuit breaker protection and photocell operated lighting control in one unit. |
Enclosure Features
- NEMA 12 enclosure fabricated from 14 ga. galvanized steel or 14 ga. T-304 stainless includes integral drip shield for protection against rain and snow.
- Continuous hinge design provides easy access to breakers and selector switch.
- Hasp and staple are provided for padlocking
- Standard Size is 36"H x 14-1/2"W x 7-3/8"D (914mm x 368mm x 187mm) to provide ample space for wiring requirements.
- Mounting tabs on top and bottom of enclosure.
- Accepts incoming power from 120/240 VAC single phase source.
|
 |
Load Center Features
- Factory installed 2-pole main breaker with 70 Amp or 100 Amp continuous rating. Factory installed branch breaker for lighting control circuitry with 20 Amp continuous rating.
- Ample space for adding plug-in breakers. Available space for installing up to 13 single pole breakers or 6 double pole breakers.
- Branch breakers available in single or double pole up to 70 Amps.
- Rated for 120/240 Volts AC, single phase, 3-wire with neutral and grounding provisions.
- Incoming power is fed through main breaker via mechanical solderless type lugs approved for Cu or Al conductors. Lugs accept incoming wire sizes from #4 through #2/0.
- "Dead-Front" trim for personnel protection.
- One piece plated copper bus.
- 22,000 RMS sym. Amperes short circuit current rating.
- Accepts Square D "QO&" series plug-in branch circuit breakers.
- NEMA 1 Enclosed Lightning Arrestor pre-wired ahead of Load Center
|
Lighting Control
- Photocell with twist-lock mounting base
- 20 Amp, 2-pole breaker for circuit protection
- 30 Amp NEMA Rated Lighting Contactor w/ 120 VAC Coil (20 Amp Tungsten Lighting Rating)
- Separate Dead Front for Lighting Control Section
- H-O-A Selector Switch for Lighting Control Operation
- Separate 10 Amp Breaker for Control Circuitry
- Plexiglass photocell viewing ports on both sides of enclosure
- Termination points for up to 10 pairs of #12 awg lighting control wires.
|
 |
Applicable Standards
All SLC II Main Breaker Load Centers with Lighting Control meet or exceed the following standards:
- NEC
- Federal Specifications WP-115c, Type 1, Class 2
- UL 508 and UL Service Entrance Equipment
|